Description Hose stream test results after fire test: Everything passed except for two soft firestops, stuffed rockwool with silicone sealant over top. The silicone let go from the sleeved and permitted water passage, preventing a fire-resistance rating for that part of the assembly in the US. Canada permits hose-stream failures.
Date
Source Own work
Author Achim Hering

Licensing edit

Public domain I, the copyright holder of this work, release this work into the public domain. This applies worldwide.
In some countries this may not be legally possible; if so:
I grant anyone the right to use this work for any purpose, without any conditions, unless such conditions are required by law.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current05:26, 23 November 2006Thumbnail for version as of 05:26, 23 November 20063,404 × 2,360 (537 KB)Achim Hering (talk | contribs){{Information |Description=Hose stream test results after fire test: Everything passed except for two soft firestops, stuffed rockwool with silicone sealant over top. The silicone let go from the sleeved and permitted water passage, preventing a [